Multi Switch
Automatic Transfer Switch
The Riello UPS Multi Switch is a high availability and versatile intelligent switch that provides redundant power to connected equipment with two AC input sources. The Riello UPS Multi Switch supplies power to the connected loads from a primary mains source. If that primary source becomes unavailable, the Riello UPS Multi Switch automatically transfers loads to the secondary source.
According to the ITI (CBEMA) chart, the transfer time from one source does not impact the operation of the connected equipment as the switching occurs safely between the two input sources regardless of any phase differences. The Riello UPS Multi Switch monitors the current and provides warnings when power consumption draws near the maximum rating which helps prevent downtime to the equipment.
Riello UPS Multi Switch has 8 independent IEC 10 A outlets allowing several devices can be plugged directly into the Rack without the need for an additional Rack PDU. The units have a connectivity slot which allows for LAN connection and remote management through PowerShield3 software, Web interface, SNMP, or SSH which makes the Riello UPS Multi Switch an ideal device for the IT manager who needs flexibility and protection for their IT equipment.
Multi Switch provides installations with power supply continuity. Its operating principle ensures higher reliability than a single UPS, (with or without its own internal bypass).
OPERATING PRINCIPLE
Multi Switch provides direct distribution of eight 10 A IEC outlets in a
system with two input power lines (two mains inputs, or two UPS). Multi
Switch is able to connect to either of the two input power lines, whilst
simultaneously monitoring the power uptake.
PROTECTION AGAINST LOAD FAULTS
If one of the loads fails (e.g. short circuit), Multi Switch disconnects the
group of sockets where the load is connected, thus preventing other loads
from being switched off (i.e. in the event of poor discrimination of the
protection devices).
PROTECTION AGAINST POWER SUPPLY FAULTS
If one of the two power sources falls outside tolerance levels, Multi Switch
will transfer the load to the second power source (switching is
instantaneous if the two sources are in phase).
Multi Switch units switch power with no impact on IT equipment. Depending on
the ITI Curve, typical power supplies will operate 20 msec. after AC voltage
drops to zero. The IEEE 1100-1999 standard also references the ITI
curve. The SSI (Server System Infrastructure) standard recommends a
hold-up time for power supplies to be a minimum of 21 msec.
for a voltage range of 100-240 V. Multi Switch units switch sources
under these industry standard times. The switching time includes the
time for the built-in intelligence to determine whether the voltage and
frequency are in range. Any point of failure in the electronics does not
cause a drop out of the output voltage because the unit incorporates
redundancy of its electronic circuitry to avoid fault tolerance.
FEATURES
- Full protection for loads against mains and load failures
- Redundant power supply
- Versatile to use: Multi Switch can be powered with 2 different power supplies (including 2 UPS of different sizes/types)
- 19” cabinet installation
- LCD Display panel
- Can be connected to PowerNetGuard supervision software
- No signal connection between the Multi Switch and the power sources or loads is necessary
- Slot for communications boards: the optional network card allows for remote in network connectivity, and management through HTTP, SNMP, and SSH protocol.
Models | MSW |
---|---|
INPUT | |
Voltage | 180-276 (selectable) |
Frequency | 50 / 60 Hz |
Switched input phases | ph+N (two poles) |
ENVIRONMENTAL | |
Color | RAL 5004 |
Communication | RS232 / Slot for communication interface |
Protection rating | IP20 |
Other compliances | EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility) |
Noise (at 1 m) | <35 dBA |
Operating temperature | 0 °C - +40 °C |
Storing temperature | -10 °C up to +50 °C |
Relative humidity | 5-95% non-condensing |
Output sockets | 8 IEC 320 10 A |
DATA | |
Weight | 10 kg |
Dimensions (h w d) | 2U x 19" x 360 mm |