Master MPS
Total protection
3:1 10-120 kVA
3:3 10-200 kVA
Master MPS series UPS devices ensure maximum
protection and power quality for any type of load, especially for mission critical
applications, data centres, security systems and electro-medical equipment,
industrial processes and telecommunications.
Master Plus is an ON LINE double conversion UPS (class VFI SS 111 in accordance with
IEC EN 62040-3) with a transformer isolated inverter.
EASY SOURCE
Master MPS makes powering UPS devices by power generators and MV/LV
transformers easier and more efficient, reducing loss in systems and coils
and correcting the power factor and eliminating harmonics by the loads
powered by the UPS itself.
In addition to this, the progressive start-up of the rectifier and the
possibility of reducing the recharge current of the batteries, allow for the
containment of the input current absorbed and therefore do not overload the
source, especially when the source is a generator.
BATTERY CARE SYSTEM: MAXIMUM BATTERY CARE
Normally the batteries are kept charged by the rectifier; when mains power
fails, the UPS uses this energy source to power its utilities. Therefore,
proper battery care is critical to ensuring correct UPS operation in
emergency conditions.
Battery Care System consists of a series of features and capabilities that
allow for battery management in order to obtain the best performance
possible and extend their operating life.
Master MPS is also compatible with different battery technologies: vented open lead acid, VRLA AGM, Gel, NiCd, Flywheels, Supercaps and Lithium.
FLEXIBILITY
Master MPS is suited to all types of applications, from computers to the most
demanding industrial environments.
Thanks to the broad range of accessories and options, complex architectures
and configurations can be created to ensure maximum power to critical loads:
expansions (in redundancy or power) may be made in already-operating
parallel systems, even without having to switch off any UPS that are already
operating and thus, maintaining power to utilities.
MAXIMUM RELIABILITY AND AVAILABILITY
Distributed or centralised parallel up to 8 units per redundant (N+1) or
powerparallel. A parallel between models with different power levels is
possible. Maximum levels of availability also in the event of an
interruption to the parallel bus cable: the system is “FAULT TOLERANT”.
It is not affected by connection cable faults and continues powering the
load without a continuity solution, signalling the anomaly with an alarm.
OPTIONS
- UGS - UPS Group Synchroniser
Allows 2 or more non-parallel UPS devices to remain synchronised even during mains power failure. The UGS also enables a Riello UPS to be synchronised with another power source that is independent and of a different power rating. - PSJ - Parallel Systems Joiner
Allows two groups of UPS to be connected in parallel whilst operating, in the event of maintenance (with no interruption to the output), using a power coupling switch. Should one of the UPS in one of the parallel groups fail, it is automatically excluded.
The PSJ connects the remaining UPS, to the other parallel group via an external bypass, in order to continue to guarantee load redundancy.
SPECIFIC SOLUTIONS
The UPS can be adapted to meet your requirements. Contact TEC to discuss the feasibility of specific solutions and options not listed in the catalogue.
Models | MPM 10 |
---|---|
INPUT | |
Voltage | 380 / 400 / 415 V three-phase |
Frequency | 45 - 65 Hz |
Frequency tolerance | ±2% (selectable from ±1% to ±5% from front panel) |
Soft start | 0 - 100% in 120 sec (selectable) |
Voltage Range | 400 V +20% -25% |
BY PASS | |
Rated voltage | 220 / 230/ 240 V single-phase + N |
Rated frequency | 50 or 60 Hz (selectable) |
OUTPUT and INVERTER OUTPUT | |
Rated power | 10000 VA |
Active power | 9000 W |
Output Voltage | 220 / 230 / 240 V single-phase + N (selectable) |
Crest factor (Ipeak/Irms) | 3 : 1 |
Static stability | ±1% |
Dynamic stability | ±5% in 10 ms |
Frequency | 50 or 60 Hz (selectable) |
Voltage distortion with non-linear load | <3% |
Voltage distortion with linear load | <1% |
Frequency stability | 0.05% |
Overload | 110% for 60 min.; 125% for 10 min.; 150% for 1 min. |
BATTERIES | |
Type | VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels |
ENVIRONMENTAL | |
Color | Dark grey RAL 7016 |
Communication | Double RS232 + dry contacts + 2 slots for communications interface |
Protection rating | IP20 |
Line-Interactive/Smart Active efficiency | Up to 98% |
Noise (at 1 m) | 60 [dBA±2] (ECO Mode) |
Operating temperature | 0 °C - +40 °C |
Relative humidity | 5-95% non-condensing |
Standards | European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111 |
DATA | |
Weight | 200 kg |
Dimensions (h w d) | 1400x555x740 mm |