Master Switch Single Phase
Static Transfer Switch
Master Switch Single-phase (MMS) is part of the Master
Switch range and offers solutions suitable for protecting singlephase loads with
different power ratings.
MMS is available in three sizes - 32, 63 and 120 A - and is, therefore, able to
satisfy various requirements for the protection of single-phase loads.
FLEXIBILITY OF USE
All MMS versions are designed with criteria that facilitate on-site
installation as well as diagnostics, control and maintenance
operations. All models are equipped with a manual bypass and the
hot-swap function allows for rapid corrective interventions by
non-specialised personnel in the event of faults.
LOAD PROTECTION
With MMS transfer switch loads are protected against critical environmental
situations and mains power interference. Microprocessor control and the use
of thyristor static switches ensure continuous monitoring of the power
supply sources and reduced switching times between the two sources in the
event of a fault.
The constant monitoring of the output current allows for the rapid
identification of any short circuit currents in the consumers, preventing
short circuits from propagating to other loads.
MMS is equipped with thermal-magnetic protection for the two sources,
ensuring rapid intervention in the event of faults and integrated back feed
protection.
MMS ensures switching times between the two power sources of less that a
quarter of a cycle, both in the event of manual switching and in the event
automatic switching triggered by a fault in the power source.
COMPLETE DIAGNOSTICS
All MMS versions are equipped with 32-character LCD displays and control
panels with multi-function keys.
This allows for rapid and intuitive monitoring of supply readings, switch
status and environmental conditions. MMS is equipped with three standard
programmable dry contacts, an input for emergency shutdown, a RS232 serial
connection and a slot for housing the expansion board, thus ensuring
complete availability of interface solutions for remote control and
monitoring.
Models | MMS 32 |
---|---|
INPUT | |
Voltage | 220 / 230 / 240 V single-phase + N |
Voltage tolerance | 180-264 (selectable) |
Frequency tolerance | ±10% (selectable) |
Input frequency | 50 / 60 Hz |
Switched input phases | ph+N (two poles) |
Distribution compatibility | IT, TT, TNS, TNC |
ENVIRONMENTAL | |
Color | RAL 7016 |
Protection rating | IP20 |
Other compliances | EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility) |
Noise (at 1 m) | < 40 dBA |
Operating temperature | 0 °C - +40 °C |
Storing temperature | -10 °C up to +50 °C |
Relative humidity | 5-95% non-condensing |
Transport | “Break Before Make” (no overlapping sources) |
Available transfer modes | Automatic / Manual / Remote |
DATA | |
Weight | 10 kg |
Dimensions (h w d) | 2U x 19” x 520 mm |