Reliable power for a sustainable world
Master Industrial
Power Range: 30 - 80 kVA
3:1

DC BUS 220 Vdc
Ideal for industrial installations

Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing and petrochemical processes, electrical distribution and power plants.
Master Industrial is an ON LINE double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.

Request Information »

INDUSTRIAL ENVIRONMENT  
Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.

HIGH ICC
The high short circuit current (ICC = 3xIn) makes it suitable for loads that require high current peaks during switch-on or during normal operation.

DC VOLTAGE 220 V
The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

REDUNDANT VENTILATION 
Redundant ventilation at 100% load is standard, ensuring operation with a normal load with half of the fans operating; in addition, each fan is monitored and an alarm signal is provided in the event of failure. The Easy Source input features, the Battery Care System, and the flexibility and communications capabilities are the same as those of the conventional Master MPS range.

Brochures and data sheets

Master Industrial

30-80 kVA DC BUS 220 Vdc

Select File Language:
en
it
de
es
fr
hu
nl
pl
ro
ru
vn
zh
Technical specifications of the model
PDF
RTF
Models MIM 30
INPUT
Rated power 30000 VA
Voltage 400 V three-phase
Voltage tolerance 400 V ±20% @full load
Frequency 50 or 60 Hz with autorange
Frequency tolerance 45 - 65 Hz
Power factor >0.93
Current distorsion <6%
Soft start 0-100% in 120" configurable
BY PASS
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ±15% (selectable from ±10% to ± 25% from front panel)
Rated frequency 50 or 60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Rated current 145 A
Number phases 3
Back-feed protection yes
OUTPUT and INVERTER OUTPUT
Rated power 30000 VA
Active power 24000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Static stability ±1%
Dynamic stability ±5%
Frequency 50 or 60 (configurable)
Voltage distortion with non-linear load <3%
Voltage distortion with linear load 1% (typical) 2% (max)
Frequency stability ±2 (configurable from ±1% to ±5% from control panel)
Inverter efficiency at rated load 91% %
Overload 110% for 60 min.; 125% for 10 min.; 150% for 1 min.
RECTIFIER OUTPUT
Ripple <1%
BATTERIES
Type Maintenance-free sealed lead-acid
Maximum recharge current 0.2xC10
ENVIRONMENTAL
Color Light grey RAL 7035
Remote controls ESD and bypass
Protection rating IP20
Cooling (type) redundant fans (front-top)
AC/AC efficiency 92.5%
Noise (at 1 m) 68-70 dBA
Remote signals dry contacts
Operating temperature 0 ÷ 40 °C
Relative humidity 5-95% non-condensing
Standards European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
DATA
Weight 640 kg
Dimensions (h w d) 1900x800x800 mm